Skip to content

Motor Drives & Controls

DC Bus Capacitor Reforming for Servo Drives and Servo Amplifiers

Servo drives and servo amplifiers that sit unused for 12 months or longer can experience deterioration of the dielectric layer inside their DC bus capacitors. Applying full power suddenly can cause excessive leakage current, overheating, or capacitor failure.

Capacitor reforming gradually restores the dielectric layer before the equipment is returned to operation.

Preparation

Inspection Before Capacitor Reforming

  • Disconnect the servo drive or servo amplifier from all motor loads
  • Visually inspect for bulging capacitors or leaking electrolyte

Reforming Procedure

DC Bus Capacitor Reforming Using a Variac

Setup

Connect a variable AC transformer (0–130VAC or 0–240VAC depending on drive voltage) to the Input L1/L2 (single-phase) or L1/L2/L3 (three-phase) terminals.

Stage 1: Low Voltage

Apply 30–40VAC (for 230V drives) or 60–80VAC (for 480V drives) for 30–60 minutes.

Stages 2–4: Gradual Voltage Increase

Increase the voltage in steps - 25%, 50%, 75%, 100% of nominal input voltage, holding each step for 30–60 minutes.

Final Stage: Full Rated Voltage

Apply full rated AC voltage for 1 hour.

Verification

Monitor the DC bus voltage (labeled DC+ and DC- or + and -) with a voltmeter; it should rise slowly and stabilize without excessive heat or noise from the capacitors.

Alternative Procedure

Reforming Using a Regulated DC Power Supply

Sometimes it is not possible to slowly increase DC bus voltage with a variable AC transformer. In this case, capacitors are reformed with direct connection of regulated DC power supply to the DC bus, and voltage is increased in steps - 25%, 50%, 75%, 100% of nominal DC bus voltage, holding each step for 30–60 minutes.

Final Stage

Apply full rated AC voltage for 1 hour.

Brands We Stock & Refurbish

Servo Drive & Amplifier Manufacturers